Substation Ground Grid Interconnection to Distribution System Neutral

Home » Substation Ground Grid Interconnection to Distribution System Neutral

Key Takeaways

  • Why interconnecting a substation ground grid to the distribution neutral can dramatically reduce Ground Potential Rise (GPR).

  • How neutral interconnection lowers induced voltages on communication cables by nearly 50%.

  • What impedance threshold ensures compliance with the 5 kV GPR safety limit.

  • How touch and step voltages remain within safe limits under both configurations.

  • Practical recommendations for bonding, surge protection, and ongoing impedance monitoring.

⏱ Estimated reading time: 6–7 minutes.


 

1. Introduction

This study investigates whether a substation ground grid should be interconnected to the distribution system neutral. The site under consideration includes a joint-use communications cable installed on the same pole line as a 4.16/2.4 kV distribution line for a distance of 300 m.

Two alternatives are analyzed:

  1. Alternative 1 – Interconnection: Substation ground grid bonded to the utility system neutral. (Measured neutral impedance: Zn = 1.4 Ω).
  2. Alternative 2 – No Interconnection: Entire fault return current flows through earth.

The study evaluates Ground Potential Rise (GPR), touch and step voltages, and induced voltage on communication cables for both alternatives, in accordance with applicable electrical safety standards and recommended practices.

2. System and Ground Grid Data

The system and supply line data, substation main grounding grid and substation ground grid expansion given below.

2.1 Electrical System Data

ParameterValue
Supply Voltage44 kV, 3-wire, effectively grounded
Supply Line Conductor556 kCM, horizontal configuration
Line Length0.932 miles
Source – Symmetrical 3-Phase Fault6.626 kA
Source – Symmetrical -G Fault4.310 kA
Line ImpedancesR(+ve) = 0.1680 Ω/mileX(+ve) = 0.5856 Ω/mile

Ro = 0.4542 Ω/mile

Xo = 2.9895 Ω/mile

System and supply line data

2.2 Substation Grounding Data

The ground grid data are provided in the following tables.

Substation main ground grids
Buried conductor length205 m
Buried conductor size2/0 AWG
Ground rods20

 

Combined main and supplementary ground grids
Buried conductor length850 m
Buried conductor size2/0 AWG
Ground rods53 (Spaced at 15m in grid #1 and 7.5m in grid #2)

 

Substation main grounding grid

 

 

 

Substation ground grid expansion

 

3. Grounding Performance Without Neutral Interconnection

Computed QuantityMain Grid OnlyMain + Extended GridCode Limit
Grid Resistance (Rg)5.662 Ω2.59 Ω
Ground Grid Current (Ig*)2605 A3182 A
Max. GPR14,750 V8,241 V5,000 V
Max. Touch Potential400 V280 V885 V
Max. Step Potential277 V60 V3,143 V

*(Ig) = Vn/(Zs + Rg)

Observation: Even with an extended ground grid, GPR remains above the 5 kV code limit. Therefore, the local distribution utility was approached to grant permission for interconnecting the substation ground grid to the available neutral associated with the 4.16/2.4 kV distribution system.

4. Neutral Interconnection Analysis

The fall-of-potential method was used to measure the utility system neutral impedance. The results are shown in following figure. Results were plotted and the utility system neutral impedance value was found to be:

  • Zn = 1.4 Ω at 62% probe distance.

 

 

By connecting the grounding grid to the utility system neutral, the resulting circuit model can be represented as follows:

The GPR was calculated using various utility neutral impedance values Zn to establish the threshold at which the allowable limit is attained:

 

Zn (W)Zs  (W)Rg//Zn (W)Zs+(Rg//Zn) (W)Total Fault CurrentIt (A)Grid/Earth CurrentIe (A)Neutral CurrentIn (A)GPRIe x Rg

(V)

1.07.210.968.16311353030013001
1.47.211.328.50298569628163947
1.57.211.418.58296173627774165
1.9167.211.758.89285888326094999
27.211.828.95284091125775154

 

With the neutral resistance at 1.4 W, the calculated GPR value was found to be 3947V, which is below the required code limit. The threshold for the GPR to be below 5000V is 1.916 W.

  • Threshold: To maintain GPR ≤ 5,000 V, Zn ≤ 1.916 Ω.
    Measured Zn = 4 Ω → acceptable.

5. Induced Voltage on Communication Cables

Since there was a joint-use installation on the pole line carrying the system neutral for a distance of 300m, the utility granted permission to interconnect the substation ground grid to the system neutral and requested that the induced voltage on the communication cables be calculated. The following calculations were conducted to find out the values of the induced voltage with and without the ground grid interconnection to the system neutral.

5.1 Alternative 1 – Interconnected Neutral (Zn = 1.4 Ω)

The calculated currents in the phase, neutral and earth return are based on the ground grid analysis. The induction calculations will be based on the currents corresponding to a system neutral impedance of 1.4 W.

Current components representation

 

The total fault current is the vectorial sum of the return current through the system neutral and the return current through the earth. They can be represented as follows:

 

Vectorial representation of ground fault current components

The numerical values of the current components are:

Current components
In2816Ð0 o = 2816 + j 0
Ie697Ð83o = 85 + j 692
It2985Ð13.6o = 2901 + j 692

 

Induced voltage due to the portion of current returning through the neutral conductor can be calculated as:

Da’xDistance between communication cable and neutral conductor4′
DaxDistance between communication cable and faulted phase conductor16′
InNeutral current during fault2816Ð0° (A)

 

Induced voltage due to the portion of current returning through the earth can be calculated as:

DexDistance between communication cable and equivalent earth returnDe – Dax
DaxDistance between communication cable and faulted phase conductor16′
DeDistance between faulted phase conductor and equivalent earthreturn
ΔEarth resistivityΩ.m
fSystem frequency60 (Hz)

 

Since Δ varies, De will vary and hence Dex. Giving Δ different typical values following results are obtained:

ΔDeDexLog10 (Dex/Dax)Vxe
25139413781.935-365.97-365.97
100278927732.239-424.64-424.64
1000881888022.740-521.62-521.62
200012471124552.891-550.76-550.76
500019718197023.090-589.26-589.26

 

The magnitude of Induced voltage can be calculated as below which is approximately between 130 to 160V.

Earth Resistivity (Ω·m)Induced Voltage (V/mile)Induced Voltage (V/300 m)
25690.6128.8
100729.3136.0
1,000798.7148.9
2,000820.6153.0
5,000850.4158.6

 

5.2 Alternative 2 – No Interconnection

This alternative calculates the induced voltage in the communication cable if the system neutral and the substation ground grid are NOT interconnected. The entire fault current will return through the earth.

The system impedance at the substation7.21Ð82.1° (W)
The resistance of main substation ground grid5.66 (W)
The magnitude of the total impedance (grid + system)9.75 (W)
The magnitude of the phase to ground fault current (If)2605 (A)

 

Since Δ varies, De will vary and hence Dex. Giving Δ different typical values following results are obtained:

Earth Resistivity (Ω·m)Induced Voltage (V/mile)Induced Voltage (V/300 m)
251430.0266.7
1001648.0307.3
1,0002010.0374.8
2,0002119.0395.1
5,0002263.0421.9

 

The induced voltage is approximately 270 to 420V (higher than alternative 1).

Observation: Interconnection reduces induced voltage by ~50% for all resistivity values.

6. Conclusion and Recommendations

Conclusion:

  • Interconnecting the substation ground grid to the distribution neutral (Zn = 1.4 Ω) reduces GPR from above code limits to 3,947 V, meeting safety requirements.
  • It also reduces induced voltages on communication cables from ~270–420 V to ~130–160 V.
  • Touch and step voltages remain within permissible limits.
  • For Zn ≤ 1.916 Ω, GPR remains ≤ 5 kV.

Recommendations:

  1. Bond substation ground grid to distribution neutral under continuous monitoring of neutral impedance.
  2. Bond communications cable messenger strand to neutral at 300 m intervals. It should be also noted that a phase to ground fault on the 44kV line will be similar to alternative 2 in this case; resulting in high induced voltages on communication circuits.
  3. Install surge protection at communication entry points.
  4. Periodically verify Zn and Rg to ensure compliance.
  5. Update maintenance procedures to reflect interconnection configuration