Substation Ground Grid Interconnection to Distribution System Neutral

  1. Home
  2. »
  3. Past Projects
  4. »
  5. Substation Ground Grid Interconnection to…

Key Takeaways

  • Why interconnecting a substation ground grid to the distribution neutral can dramatically reduce Ground Potential Rise (GPR).

  • How neutral interconnection lowers induced voltages on communication cables by nearly 50%.

  • What impedance threshold ensures compliance with the 5 kV GPR safety limit.

  • How touch and step voltages remain within safe limits under both configurations.

  • Practical recommendations for bonding, surge protection, and ongoing impedance monitoring.

⏱ Estimated reading time: 6–7 minutes.


 

1. Introduction

This study investigates whether a substation ground grid should be interconnected to the distribution system neutral. The site under consideration includes a joint-use communications cable installed on the same pole line as a 4.16/2.4 kV distribution line for a distance of 300 m.

Two alternatives are analyzed:

  1. Alternative 1 – Interconnection: Substation ground grid bonded to the utility system neutral. (Measured neutral impedance: Zn = 1.4 Ω).
  2. Alternative 2 – No Interconnection: Entire fault return current flows through earth.

The study evaluates Ground Potential Rise (GPR), touch and step voltages, and induced voltage on communication cables for both alternatives, in accordance with applicable electrical safety standards and recommended practices.

2. System and Ground Grid Data

The system and supply line data, substation main grounding grid and substation ground grid expansion given below.

2.1 Electrical System Data

Parameter Value
Supply Voltage 44 kV, 3-wire, effectively grounded
Supply Line Conductor 556 kCM, horizontal configuration
Line Length 0.932 miles
Source – Symmetrical 3-Phase Fault 6.626 kA
Source – Symmetrical -G Fault 4.310 kA
Line Impedances R(+ve) = 0.1680 Ω/mileX(+ve) = 0.5856 Ω/mile

Ro = 0.4542 Ω/mile

Xo = 2.9895 Ω/mile

System and supply line data

2.2 Substation Grounding Data

The ground grid data are provided in the following tables.

Substation main ground grids
Buried conductor length 205 m
Buried conductor size 2/0 AWG
Ground rods 20

 

Combined main and supplementary ground grids
Buried conductor length 850 m
Buried conductor size 2/0 AWG
Ground rods 53 (Spaced at 15m in grid #1 and 7.5m in grid #2)

 

Substation main grounding grid

 

 

 

Substation ground grid expansion

 

3. Grounding Performance Without Neutral Interconnection

Computed Quantity Main Grid Only Main + Extended Grid Code Limit
Grid Resistance (Rg) 5.662 Ω 2.59 Ω
Ground Grid Current (Ig*) 2605 A 3182 A
Max. GPR 14,750 V 8,241 V 5,000 V
Max. Touch Potential 400 V 280 V 885 V
Max. Step Potential 277 V 60 V 3,143 V

*(Ig) = Vn/(Zs + Rg)

Observation: Even with an extended ground grid, GPR remains above the 5 kV code limit. Therefore, the local distribution utility was approached to grant permission for interconnecting the substation ground grid to the available neutral associated with the 4.16/2.4 kV distribution system.

4. Neutral Interconnection Analysis

The fall-of-potential method was used to measure the utility system neutral impedance. The results are shown in following figure. Results were plotted and the utility system neutral impedance value was found to be:

  • Zn = 1.4 Ω at 62% probe distance.

 

 

By connecting the grounding grid to the utility system neutral, the resulting circuit model can be represented as follows:

The GPR was calculated using various utility neutral impedance values Zn to establish the threshold at which the allowable limit is attained:

 

Zn (W) Zs  (W) Rg//Zn (W) Zs+(Rg//Zn) (W) Total Fault CurrentIt (A) Grid/Earth CurrentIe (A) Neutral CurrentIn (A) GPRIe x Rg

(V)

1.0 7.21 0.96 8.16 3113 530 3001 3001
1.4 7.21 1.32 8.50 2985 696 2816 3947
1.5 7.21 1.41 8.58 2961 736 2777 4165
1.916 7.21 1.75 8.89 2858 883 2609 4999
2 7.21 1.82 8.95 2840 911 2577 5154

 

With the neutral resistance at 1.4 W, the calculated GPR value was found to be 3947V, which is below the required code limit. The threshold for the GPR to be below 5000V is 1.916 W.

  • Threshold: To maintain GPR ≤ 5,000 V, Zn ≤ 1.916 Ω.
    Measured Zn = 4 Ω → acceptable.

5. Induced Voltage on Communication Cables

Since there was a joint-use installation on the pole line carrying the system neutral for a distance of 300m, the utility granted permission to interconnect the substation ground grid to the system neutral and requested that the induced voltage on the communication cables be calculated. The following calculations were conducted to find out the values of the induced voltage with and without the ground grid interconnection to the system neutral.

5.1 Alternative 1 – Interconnected Neutral (Zn = 1.4 Ω)

The calculated currents in the phase, neutral and earth return are based on the ground grid analysis. The induction calculations will be based on the currents corresponding to a system neutral impedance of 1.4 W.

Current components representation

 

The total fault current is the vectorial sum of the return current through the system neutral and the return current through the earth. They can be represented as follows:

 

Vectorial representation of ground fault current components

The numerical values of the current components are:

Current components
In 2816Ð0 o = 2816 + j 0
Ie 697Ð83o = 85 + j 692
It 2985Ð13.6o = 2901 + j 692

 

Induced voltage due to the portion of current returning through the neutral conductor can be calculated as:

Da’x Distance between communication cable and neutral conductor 4′
Dax Distance between communication cable and faulted phase conductor 16′
In Neutral current during fault 2816Ð0° (A)

 

Induced voltage due to the portion of current returning through the earth can be calculated as:

Dex Distance between communication cable and equivalent earth return De – Dax
Dax Distance between communication cable and faulted phase conductor 16′
De Distance between faulted phase conductor and equivalent earthreturn
Δ Earth resistivity Ω.m
f System frequency 60 (Hz)

 

Since Δ varies, De will vary and hence Dex. Giving Δ different typical values following results are obtained:

Δ De Dex Log10 (Dex/Dax) Vxe
25 1394 1378 1.935 -365.97 -365.97
100 2789 2773 2.239 -424.64 -424.64
1000 8818 8802 2.740 -521.62 -521.62
2000 12471 12455 2.891 -550.76 -550.76
5000 19718 19702 3.090 -589.26 -589.26

 

The magnitude of Induced voltage can be calculated as below which is approximately between 130 to 160V.

Earth Resistivity (Ω·m) Induced Voltage (V/mile) Induced Voltage (V/300 m)
25 690.6 128.8
100 729.3 136.0
1,000 798.7 148.9
2,000 820.6 153.0
5,000 850.4 158.6

 

5.2 Alternative 2 – No Interconnection

This alternative calculates the induced voltage in the communication cable if the system neutral and the substation ground grid are NOT interconnected. The entire fault current will return through the earth.

The system impedance at the substation 7.21Ð82.1° (W)
The resistance of main substation ground grid 5.66 (W)
The magnitude of the total impedance (grid + system) 9.75 (W)
The magnitude of the phase to ground fault current (If) 2605 (A)

 

Since Δ varies, De will vary and hence Dex. Giving Δ different typical values following results are obtained:

Earth Resistivity (Ω·m) Induced Voltage (V/mile) Induced Voltage (V/300 m)
25 1430.0 266.7
100 1648.0 307.3
1,000 2010.0 374.8
2,000 2119.0 395.1
5,000 2263.0 421.9

 

The induced voltage is approximately 270 to 420V (higher than alternative 1).

Observation: Interconnection reduces induced voltage by ~50% for all resistivity values.

6. Conclusion and Recommendations

Conclusion:

  • Interconnecting the substation ground grid to the distribution neutral (Zn = 1.4 Ω) reduces GPR from above code limits to 3,947 V, meeting safety requirements.
  • It also reduces induced voltages on communication cables from ~270–420 V to ~130–160 V.
  • Touch and step voltages remain within permissible limits.
  • For Zn ≤ 1.916 Ω, GPR remains ≤ 5 kV.

Recommendations:

  1. Bond substation ground grid to distribution neutral under continuous monitoring of neutral impedance.
  2. Bond communications cable messenger strand to neutral at 300 m intervals. It should be also noted that a phase to ground fault on the 44kV line will be similar to alternative 2 in this case; resulting in high induced voltages on communication circuits.
  3. Install surge protection at communication entry points.
  4. Periodically verify Zn and Rg to ensure compliance.
  5. Update maintenance procedures to reflect interconnection configuration

 

Share this post on
Telegram
Email
LinkedIn
WhatsApp
Facebook
//
Our customer support team is here to answer your questions. Ask us anything!
👋 Hi, how can I help?